CVSS v3 4.9
ATTENTION: Remotely exploitable/low skill level to exploit.
Vendor: Siemens
Equipment: SIMATIC WinCC and SIMATIC WinCC Runtime Professional
Vulnerability: Denial of Service
AFFECTED PRODUCTS
Simatic wincc free download. Development Tools downloads - SIMATIC WinCC/Audit Viewer 2008 SP2 by Siemens AG and many more programs are available for instant and free download. What is SIMATIC WinCC flexible? The SIMATIC WinCC Flexible is an example of HMI software, or a human machine interface, developed by Siemens Corporation (SIMATIC is a portmanteau of “Siemens” and “automatic”; this name is under patent since 1958).
Siemens reports that the vulnerability affects the following versions of SIMATIC WinCC, SIMATIC WinCC (TIA Portal), and SIMATIC WinCC Runtime Professional:
- SIMATIC WinCC:
- V7.3: All versions prior to V7.3 Update 11, and
- V7.4: All versions prior to V7.4 SP1.
- SIMATIC WinCC Runtime Professional:
- V13: All versions prior to V13 SP2, and
- V14: All versions prior to V14 SP1.
- SIMATIC WinCC (TIA Portal) Professional:
- V13: All versions prior to V13 SP2, and
- V14: All versions prior to V14 SP1.
IMPACT
Successful exploitation of this vulnerability under certain circumstances may allow the attacker to cause the affected service to crash, resulting in a denial-of-service condition.
MITIGATION
Siemens has released updates for the following products and strongly encourages users to upgrade to the new versions as soon as possible:
- SIMATIC WinCC:
- V7.3: Update to WinCC V7.3 Update 13
- V7.4: Update to WinCC V7.4 SP1
- SIMATIC WinCC Runtime Professional:
- V13: Update to V13 SP2
- V14: Update to V14 SP1
- SIMATIC WinCC (TIA Portal) Professional:
- V13: Update to V13 SP2
- V14: Update to V14 SP1
For more information on this vulnerability and more detailed mitigation instructions, please see Siemens Security Advisory SSA-156872 at the following location:
Siemens Wincc V7.5 Download
As a general security measure Siemens strongly recommends protecting network access to SIMATIC WinCC, SIMATIC WinCC Runtime, and SIMATIC WinCC (TIA Portal) Professional stations with appropriate mechanisms. Siemens advises configuring the environment according to Siemens operational guidelines in order to run the devices in a protected IT environment.
NCCIC/ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.
VULNERABILITY OVERVIEW
An authenticated, remote attacker who is a member of the “administrators” group could crash services by sending specially crafted messages to the DCOM interface.
CVE-2017-6867 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H).
RESEARCHER
Sergey Temnikov and Vladimir Dashchenko of the Kaspersky Lab Critical Infrastructure Defense Team reported this vulnerability directly to Siemens.
BACKGROUND
Critical Infrastructure Sectors: Food and Agriculture, Chemical, Energy, Water and Wastewater Systems
Countries/Areas Deployed: Worldwide
Company Headquarters Location: Germany
Contact Information
For any questions related to this report, please contact the NCCIC at:
Email: NCCICCUSTOMERSERVICE@hq.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: http://ics-cert.us-cert.gov
or incident reporting: https://ics-cert.us-cert.gov/Report-Incident?
The NCCIC continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
1. EXECUTIVE SUMMARY
- CVSS v3 9.1
- ATTENTION: Exploitable remotely/low skill level to exploit
- Vendor: Siemens
- Equipment: SIMATIC PCS7, WinCC Runtime Professional, WinCC (TIA Portal)
- Vulnerabilities: SQL Injection, Uncaught Exception, Exposed Dangerous Method
2. UPDATE INFORMATION
This updated advisory is a follow-up to the advisory update titled ICSA-19-134-08 Siemens SIMATIC PCS7, WinCC, TIA Portal (Update B) that was published August 13, 2019, on the ICS webpage on us-cert.gov.
3. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary commands on the affected system.
4. TECHNICAL DETAILS
4.1 AFFECTED PRODUCTS
The following Siemens SIMATIC products are affected:
--------- Begin Update C Part 1 of 2 --------
- SIMATIC WinCC Runtime Professional v13: all versions
- SIMATIC WinCC Runtime Professional v14: all versions prior to v14.1 Upd 11
- SIMATIC WinCC Runtime Professional v15: all versions prior to v15.1 Upd 3
--------- End Update C Part 1 of 2 --------
- SIMATIC PCS7 v8.0 and earlier: all versions
- SIMATIC PCS7 v8.1: all versions prior to v8.1 with WinCC v7.3 Upd 19
- SIMATIC PCS7 v8.2: all versions prior to v8.2 SP1 with WinCC v7.4 SP1 Upd 11
- SIMATIC PCS7 v9.0: all versions prior to v9.0 SP2 with WinCC v7.4 SP1 Upd 11
- SIMATIC WinCC (TIA Portal) v13: all versions
- SIMATIC WinCC (TIA Portal) v14: all versions
- SIMATIC WinCC (TIA Portal) v15: all versions
- SIMATIC WinCC v7.2 and earlier: all versions
- SIMATIC WinCC v7.3: all versions prior to v7.3 Upd 19
- SIMATIC WinCC v7.4: all versions prior to v7.4 with WinCC v7.4 SP1 Upd 11SIMATIC WinCC v7.5: all versions prior to v7.5 Upd 3
4.2 VULNERABILITY OVERVIEW
4.2.1 SQL INJECTION CWE-89
An attacker with network access to the project file could run arbitrary system commands with the privileges of the local database server. This may impact the confidentiality, integrity, and availability of the affected system.
CVE-2019-10916 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H).
4.2.2 UNCAUGHT EXCEPTION CWE-248
An attacker with local access to the project file could cause a denial-of-service condition on the affected product as the project file is loaded. Successful exploitation could compromise availability of the affected system.
Simatic Wincc Free Download
CVE-2019-10917 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:L).
4.2.3 EXPOSED DANGEROUS METHOD OR FUNCTION CWE-749
An authenticated attacker with network access to the DCOM interface could execute arbitrary commands with SYSTEM privileges. Successful exploitation could compromise confidentiality, integrity, and availability of the affected system.
CVE-2019-10918 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
4.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
4.4 RESEARCHER
Vladimir Dashchenko and Sergey Temnikov from Kaspersky Lab, CNCERT/CC, and ChengBin Wang from Guoli Security Technology reported these vulnerabilities to Siemens.
5. MITIGATIONS
Siemens has an update available for the following affected products:
--------- Begin Update C Part 2 of 2 --------
- SIMATIC WinCC Runtime Professional v14: Update to v14.1 Upd 11
- SIMATIC WinCC Runtime Professional v15: Update to v15.1 Upd 3
--------- End Update C Part 2 of 2 --------
- SIMATIC PCS7 v8.1: Update WinCC to v7.3 Upd 19
- SIMATIC PCS7 v9.0: Update WinCC to v7.4 SP1 Upd 11
- SIMATIC WinCC v7.3: Update WinCC to v7.3 Upd 19
- SIMATIC PCS7 v8.2: Update WinCC to v7.4 SP1 Upd 11
- SIMATIC WinCC v7.4: Update WinCC to v7.4 SP1 Upd 11
- SIMATIC WinCC v7.5: Update WinCC to v7.5 Upd 3
Siemens Download Wincc Flexible
Siemens recommends users apply the following specific workarounds and mitigations to reduce risk until updates or patches are available:
- Apply defense-in-depth strategies.
- Enable “Encrypted communication” in SIMATIC WinCC and SIMATIC PCS7.
- Only open project files from trusted locations.
As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends users configure their environment according to the Siemens operational guidelines for industrial security and follow the recommendations in the product manuals.
Additional information on industrial security by Siemens can be found at:
For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens security advisory SSA-697412 at the following location:
Siemens Wincc Comfort Download
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Siemens Wincc 6.2 Download
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.
Wincc 7.4 Sp1 Download
Contact Information
Siemens Wincc 7.5 Download
For any questions related to this report, please contact the NCCIC at:
Email: NCCICCUSTOMERSERVICE@hq.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: http://ics-cert.us-cert.gov
or incident reporting: https://ics-cert.us-cert.gov/Report-Incident?